Generator
What is the smallest generator that holds?
Viable, borderline and unsuitable thresholds based on the real peak. Average load, overload, litres and euros.
Before you rent a generator, measure. Before you invest in a battery, simulate. Your measured curve becomes your site's energy twin: VISU Live tests over 130 generator × battery combinations on it, and recommends the cheapest one that holds the peak. In litres, euros and CO₂.
Real anonymised example: one week measured on the main switchboard of a large venue. Curve redrawn.
71kW
Measured peak
over one week, minute by minute37kW
Average load
barely half the peak100kVA
Generator needed alone
to hold the peak60 kVA
+ 100 kWh battery
Recommended combination−40% installed generator powerThe video feeder of a live production, measured by the VISU Box from set-up to the last show. Then replayed in VISU Live with every generator and battery option. Real data, anonymised.
9,799L
Fuel saved
−92% versus the generator in place14,925€
Costs avoided
fuel and pack rental included26t
CO₂ avoided
over 4.5 days of operation58%of the time
Generator off
the battery takes over, with no outageSet-up, rehearsals, stand-by, shows: each phase is split out and quantified. One brief peak at 105 kW, but a load mostly below 50 kW.
| Option | Fuel | Estimated cost | CO₂ | Verdict |
|---|---|---|---|---|
| Generator in place | 10,633 L | €17,012 | 28.3 t | Oversized |
| 100 kVA generator only | 1,229 L | €2,720 | 3.3 t | Viable −88% |
| 100 kVA generator + 500 kWh battery | 833 L | €2,087 | 2.2 t | Recommended −92% |
| 1 MWh battery only | — | — | — | Unsuitable 3,488 kWh needed |
Costs calculated by VISU Live: fuel, plus pack rental for the hybrid option. Over 130 generator × battery combinations tested, 30 ruled out as unsuitable.
The 100 kVA generator runs at 80 kW, in its efficient range, and recharges the battery. The rest of the time it stops: the battery supplies the load alone, with no outage. Its state of charge never drops below 31%.
Curves redrawn from the real study.
Each mode replays your measured week, minute by minute.
What is the smallest generator that holds?
Viable, borderline and unsuitable thresholds based on the real peak. Average load, overload, litres and euros.
Can a battery relieve the generator?
Two strategies: shave the peaks, or switch the generator off at low load overnight. Generator-off hours, fuel and CO₂ avoided.
Can we do without a generator?
Minimum capacity required, autonomy, grid recharging over a chosen time window.
Which combination costs least?
Over 130 generator × battery combinations tested. The cheapest viable one is recommended, fuel and rental included.
Simulations use a catalogue of market generators and battery packs, with a “real load” consumption model.
VISU sells neither generators nor batteries. When a solution does not hold, the tool says so, with figures. You invest in what works, not in what someone wants to sell you.
The VISU Box records your site's real load, feeder by feeder. Installed in under an hour, with no shutdown.
VISU Live replays the measured period with every generator × battery combination, and rules out those that do not hold.
You get the recommended combination in litres, euros and CO₂. A report ready to present.